Skip to main content
ABB TotalFlow Driver Setup
Module Setup
Creating/Configuring an Analyzer/GC Device
- Create it with the following settings:
- Name
- Device
- Connectivity
- Hostname: (Device IP Address)
- TCP Port: (Typically 9999)
- Auto Setup
- Enable Auto-Discovery: Checked
- Add All Totalflow Application Definitions: Unchecked
- Add All Array-Register Definitions: Checked
- Auto-generate Templates and Poll Group: Unchecked
- Auto-publish Meter Config: Unchecked
- Click More -> TotalFlow Applications
- Enable polling on the following apps:
- 0 - System
- 30 - GCM Main
- 38 - Stream 1
- 39 - Stream 2 (Optional)
- 40 - Stream 3 (Optional)
- 41 - Stream 4 (Optional)
- 46 - Controller
- Click More -> Array Register Templates
- Click More -> Poll Groups
- Add a Poll Group with a generic name: "Default Poll Group"
- Edit "Poll Group Contents" and add the following rows
- System
- Array-Register Template: System
- Application Name: System
- Enabled: Checked
- Scan Rate: (desired poll rate in seconds - default: 60)
- Tag Folder Path: System
- GCM
- Array-Register Template: GCM Interface
- Application Name: GCM MAIN - He
- Enabled: Checked
- Scan Rate: (desired poll rate in seconds - default: 60)
- Tag Folder Path: GCM
- Controller
- Array-Register Template: Controller
- Application Name: Ctrl-1
- Enabled: Checked
- Scan Rate: (desired poll rate in seconds - default: 60)
- Tag Folder Path: Controller
- Streams 1-4
- Array-Register Template: ABB GC Stream
- Application Name: (Stream [1-4] Application Name)
- Enabled: Checked
- Scan Rate: (desired poll rate in seconds - default: 60)
- Tag Folder Path: Stream [1-4]
- Click Edit to edit the device and change the following settings:
- Auto Setup
- Enable Auto-Discovery: Unchecked
- Add All Array-Register Definitions: Unchecked
Creating/Configuring a Flow Meter
- Create it with the following settings:
- Name
- Device
- Connectivity
- Hostname: (Device IP Address)
- TCP Port: (Typically 9999)
- Auto Setup
- Enable Auto-Discovery: Checked
- Add All Totalflow Application Definitions: Unchecked
- Add All Array-Register Definitions: Checked
- Auto-generate Templates and Poll Group: Unchecked
- Auto-publish Meter Config: Unchecked
- Click More -> TotalFlow Applications
- Enable polling on the following apps:
- 0 - System
- 7 - I/O Interface
- 11 - Flow Meter (Tube)
- Click More -> Array Register Templates
- Click More -> Poll Groups
- Add a Poll Group with a generic name: "Default Poll Group"
- Edit "Poll Group Contents" and add the following rows
- System
- Array-Register Template: System
- Application Name: System
- Enabled: Checked
- Scan Rate: (desired poll rate in seconds - default: 60)
- Tag Folder Path: System
- Power
- Array-Register Template: Power
- Application Name: I/O Interface
- Enabled: Checked
- Scan Rate: (desired poll rate in seconds - default: 60)
- Tag Folder Path: Power
- Flow Meter
- Array-Register Template: Flow Meter
- Application Name: (Flow Meter Name/ID)
- Enabled: Checked
- Scan Rate: (desired poll rate in seconds - default: 60)
- Tag Folder Path: Flow Meter
- Click Edit to edit the device and change the following settings:
- Auto Setup
- Enable Auto-Discovery: Unchecked
- Add All Array-Register Definitions: Unchecked